On a high-run-time process load, Newsome chillers cost up to 42% less to run than comparable hire chillers. That’s an average of 39% across five size bands, worth £57k to £233k a year per chiller at 8,000 hrs and £0.32/kWh. Efficiency is the lead message: Aggreko, ICS Cool Energy, Daikin and Celsius Hire publish no EER figures on their hire pages at all. It’s backed by process-grade hardware the generalist fleets don’t standardise on: coated microchannel coils, shell and tube evaporators, twin circuits, an on-board pump and tank, BACnet-ready controls and R454B on the Mitsubishi range. 

The comparison uses each competitor’s own published datasheets (Cross Rental and Aqua Cool), with our best unit in each band against their weakest. A more conservative like-for-like case is shown alongside so sales have a defensible fallback. 

The market

UK chiller hire splits into three camps: global giants selling scale, OEM rental arms selling the badge, and regional specialists selling service. Almost all of them compete on availability and response time. None leads on running cost.

Company  Type  Chiller range  How they pitch it  Efficiency message 
Aggreko  Global rental  50–800kW air-cooled, 1.5MW water-cooled, LT/VLT units  “World’s largest fleet”, turnkey solutions  None published 
ICS Cool Energy  Manufacturer + hire (MTA i-Chiller)  3kW–1.4MW, +15°C to −40°C  500MW+ fleet, average age under 1.5 yrs, same/next-day delivery, remote monitoring  “EcoDesign compliant” only 
Cross Rental Services  National multi-product hire  100–500kW on brochures, multi-MW packages  Integral pump and tank; depots in Andover, Birmingham, Stoke, Haydock, Glasgow, Kent; £500k into fleet telemetry  Prints EER 2.5–3.1, all R410A 
Aqua Cooling  Process cooling specialist, hire since 2016  ~4kW–560kW+ (Aqua Pro range)  Process-focused, Y-strainers, vented or pressurised, low-GWP R454B on newer units  Prints “Excellent EER” 3.3–4.1 
Celsius Hire  Regional specialist (Eastleigh)  7–900kW, LT and ultra-LT, heat pump chillers  Fixed monthly cost incl. servicing, managed service, flexible contracts  None published 
Daikin Rental Solutions  OEM rental arm  50kW–1MW air and water-cooled  Daikin on Site remote monitoring on every unit, BMS plug-and-play, contingency planning  “Efficiency”, no figures 
Carrier Rental Systems  OEM rental arm  AquaSnap scroll, ~220–400kW+  Rugged steel frames, fast deployment  None published 
Andrews Sykes  National hire, 25 depots  Chillers plus FC90 fast-chill air units to −10°C  4-hour response from 25 depots (2015 claim)  None published 

 

Two things stand out. First, Cross Rental is the weakest on efficiency: their whole published fleet runs on R410A, and the brochures mix 30°C and 35°C rating points. Second, Aqua Cool is the most direct rival on process credentials and the only one that prints EER as a selling point. That makes it the competitor sales will most often be measured against.

What buyers weigh up

Beyond kW and the weekly rate, process buyers judge hire chillers on eight things. Newsome wins outright on four, holds its own on three, and has one gap to close. 

Buying factor  Why it matters to a process site  Where Newsome stands 
Running cost  On 24/7 duty, electricity outweighs the hire charge many times over  Win: EER up to 3.96 
Low-temperature capability  Glycol duty down to −10°C for food, pharma and plastics  Win: −10°C across the range, with published capacity at −10/−5°C 
Robustness and uptime  Dirty water, corrosive air and no tolerance for trips  Win: shell and tube evaporators, coated coils, twin circuits on most models 
Refrigerant and F-gas exposure  GB HFC quota drops 23% in Jan 2027; R410A up 60% in May 2026  Win: R454B (GWP 466) on the Mitsubishi range; the C-range is still R410A 
Plug-and-play hydraulics  Fewer extra hire items, faster set-up  Match: pump and tank on most models (Aqua Cool and Cross Rental offer this too) 
BMS integration  Alarms and trend data into the site system  Match/edge: BACnet-capable controllers (Daikin also claims BMS plug-and-play) 
Availability and response  Breakdown cover, same/next-day delivery  Match: needs Newsome’s own response figures to compete with ICS and Andrews’ claims 
Remote monitoring / telemetry  Proactive fault alerts, energy reporting  Gap? ICS, Daikin, Cross Rental and Celsius all advertise it. Confirm what Newsome offers 

 

Two buyer trends are pushing efficiency up the list. Business electricity averaged 24.5p/kWh in Q2 2026, and Scope 2 carbon reporting now lands on the facilities manager’s desk. A hire chiller that cuts both is an easier sell to finance than the cheapest weekly rate. 

Running costs

The headline case saves 37–42% in every band. The method: cost to deliver the Newsome unit’s rated duty, using each competitor’s published total unit power (capacity ÷ power input). Our NR-150C (EER 3.00) and the draft NR-375C sheet are left out, so we’re showing our best against their weakest. 

newsome

Source: Newsome, Cross Rental and Aqua Cool product datasheets, Oct 2026. 7/12°C water, 30°C ambient (Cross Rental 150/350kW published at 35°C). Full load, 8,000 hrs/yr, £0.32/kWh. Competitor power = their published total unit power.

Like-for-like check. Swap in the EER each competitor actually prints and the gap narrows, most sharply against Aqua Cool: 

Size band  Pairing  Headline saving £/yr  Like-for-like saving £/yr 
120kW  NR-120C vs Cross Rental 100kW  £56,650 (42%)  £25,688 (25%) 
120kW  NR-120C vs Aqua Cool 125kW  £12,225 (14%)  £12,187 (14%) 
150kW  NR-135C vs Cross Rental 150kW  £27,089 (22%)  £8,032 (8%)* 
150kW  NR-135C vs Aqua Cool 150kW  £55,074 (37%)  £8,288 (8%) 
200kW  NR-200M vs Cross Rental 200kW  £67,635 (37%)  £54,443 (32%) 
200kW  NR-200M vs Aqua Cool 160kW  £32,797 (22%)  £19,705 (14%) 
375kW  NR-375M vs Cross Rental 350kW  £61,771 (20%)  £14,046 (5%)* 
375kW  NR-375M vs Aqua Cool 340kW  £147,970 (37%)  £10,734 (4%) 
475kW  NR-475M vs Cross Rental 500kW  £233,318 (42%)  £158,720 (33%) 
475kW  NR-475M vs Aqua Cool 560kW  £210,429 (39%)  −£29,097 (−10%) 

*Cross Rental 150kW and 350kW are rated at 35°C ambient. The like-for-like column adds an estimated 15% to their EER to bring them back to 30°C. 

The swing against Aqua Cool happens because their printed EERs don’t reconcile with their own power figures. The 560kW sheet prints EER 4.1, but 557kW ÷ 246.8kW absorbed = 2.26. The printed figure looks like compressor-only. Against Cross Rental the saving holds at 25–33% whichever way you read it, so Cross Rental is the safest named comparison. The live model, with editable tariff and hours, is in Newsome_Chiller_RCA_Why_Newsome.xlsx in the project folder. 

Feature comparison 

Against the two brochures we hold, Newsome has the stronger spec on efficiency, refrigerant, coil protection, evaporator type and controls. 

Feature  Newsome  Cross Rental  Aqua Cool 
Full-load EER (7/12°C, 30°C)  3.73–3.96 (best units)  2.5–2.9 printed, 2.2–2.5 from total power  3.3–4.1 printed, 2.3–3.3 from total power 
Leaving fluid range  +20°C to −10°C  Not stated (“ice rink” capable)  −10°C to +20°C on 340/560kW 
Ambient range  −10°C to +45°C  Not stated  Not stated 
Condenser coil  Epoxy-coated aluminium microchannel  Standard coil + metallic filter grid  Standard coil + protection grid 
Evaporator  Shell and tube (tank-immersed on NR-120C)  Plate  Coaxial or shell and tube 
Refrigeration circuits  Dual independent from NR-135C up (NR-120C and NR-375C single)  Single on 100kW, dual from 150kW  Dual 
Refrigerant  R454B (M-range), R410A (C-range)  R410A throughout  R454B on newer units, R410A on others 
Integral pump and tank  Most models, 3–3.5 bar  Yes, 3 bar  Yes up to 160kW; remote pump feed on 340/560kW 
BMS protocol  BACnet-capable  Not stated  Not stated (“simple controls”) 
Brand  Mitsubishi Electric Climaveneta, Stulz Cosmotec  Mixed (Rhoss on 350kW)  Own-badged Aqua Pro 
Sound at 10m  49.6–62 dB(A)  53–62 dB(A)  Not stated 
Ecodesign  ErP 2021, SEPR HT/MT compliant  Not stated  Not stated 

Newsome’s fleet runs from NR 5 (4.4kW) to NR 750 (778kW), with published capacities at −10/−5°C, 7/12°C and 15/20°C for every model in the Rental Equipment Selector. That low-temperature data is a selection tool sales can hand straight to a process engineer. 

USPs and sales messaging

Lead with money, prove it with engineering, close on people. 

Primary line: Your chiller runs all day, every day. Ours cost less to do it. 

Proof points (short form for Qwilr, LinkedIn and the data sheet): 

  1. Up to 42% lower running costs. EERs up to 3.96. Save up to £233k a year on a 475kW process load. 
  2. Process DNA. Down to −10°C flow as standard. Built for 24/7 duty, not comfort cooling. 
  3. Coated microchannel coils. Smaller refrigerant charge, protected against aggressive sites. 
  4. Plug in and go. Pump and tank on board for most models. Nothing else to hire. 
  5. Talks to your BMS. BACnet-capable controllers, so alarms and trends land straight in your site system. 
  6. F-gas ready. R454B with 78% lower GWP than R410A. Fewer worries as the HFC quota tightens. 
  7. Twin-circuit resilience. Dual independent circuits on most models from 135kW. Lose a circuit, keep cooling. 
  8. Built for real process water. Shell and tube evaporators shrug off fouling. 
  9. Tier-one kit. Mitsubishi Electric Climaveneta and Stulz Cosmotec. 
  10. Engineers, not a hire desk. Selection, design, install and service from one group. 

Weekly framing for quotes: the hire charge is visible, the electricity isn’t. Put the saving next to the weekly rate (“this unit saves you about £1,300 a week to run”) so the buyer compares total cost, not rate card. 

Carbon framing: every £ saved at 32p is roughly 3.1kWh not drawn from the grid. Quote kWh saved per year, and let the customer apply their own Scope 2 factor (the DESNZ 2026 grid factor dropped sharply under its new method, so a hard tCO₂e figure dates quickly). 

Watch-outs

The efficiency story is strong, but a few things need handling before it goes public. 

  • Don’t name Aqua Cool in a headline comparison. The 42%/39% figures rely on reading their total absorbed power. If they push back with their printed EERs, the 475kW comparison flips in their favour. The data sheet uses “typical hire chiller” for this reason. 
  • Comparative ads must be verifiable. Under the ASA/CAP code, a named-competitor claim needs a like-for-like, documented basis. Keep the workbook and the downloaded competitor PDFs on file as substantiation. 
  • Newsome’s own data is patchy. NR-200M and NR-375M datasheets are marked “To be updated”. The NR-375C sheet is a draft built on another supplier’s template (it still says “run off a 13amp plug”). NR-475’s header reads NR-375. All Newsome figures are at 30°C rather than the 32°C Eurovent point. Tidy these before customers see them. 
  • The C-range is still R410A. The low-GWP message only holds for the Mitsubishi (M) units. NR-150C, at EER 3.00, is also no better than the competition. 
  • Twin circuits aren’t range-wide. NR-120C and NR-375C are single-circuit, so word it as “most models”. 
  • Telemetry is the obvious gap. ICS, Daikin, Cross Rental and Celsius all advertise remote monitoring. If Newsome offers it, add it as USP 11. If not, it’s the next investment to make. 
  • Service claims are missing. Competitors quote same/next-day delivery and 4-hour response. Newsome needs its own numbers (response time, depot coverage, fleet age) to compete on the non-efficiency questions. 
  • Pump and tank aren’t unique. Cross Rental and Aqua Cool fit them too, so treat this as “no compromise” rather than a differentiator. 
  • ICS Cool Energy and Celsius publish no product datasheets. They can’t be benchmarked like-for-like yet. The Eurovent directory lists ICS’s MTA kit and could fill that gap later. 