Why You Should Rent an AHU (Air Handling Unit) from Newsome
When hiring a temporary air handling unit, energy efficiency can be just as important as heating, cooling and ventilation performance. Newsome rental AHUs are designed to deliver the required environmental conditions while minimising unnecessary energy consumption, helping businesses control the total cost of their temporary HVAC installation.
Whether an air handling unit is required during planned maintenance, equipment replacement, an unexpected breakdown or a temporary increase in heating and cooling demand, selecting the right equipment can make a considerable difference to operating costs.
An AHU may need to operate for several weeks or months, sometimes continuously. During this period, electricity consumption from fans, together with the energy required to generate heating and cooling, can represent a significant proportion of the overall project cost.
At Newsome, our rental air handling units incorporate advanced fan technology, intelligent airflow control, modulating heating and cooling valves and programmable operating schedules. These features allow the equipment to respond to the actual requirements of the installation rather than consuming energy unnecessarily.
Understanding the True Cost of AHU Hire
The initial hire charge is only one element of the total cost of operating a temporary air handling unit.
Electricity consumption, associated chiller or boiler operation, installation requirements and the duration of the hire all influence the final cost.
For example, an AHU with oversized fans operating continuously at maximum speed may consume considerably more electricity than necessary. Similarly, a unit providing full heating or cooling output when demand is relatively low can increase the energy required from the connected boiler or chiller.
These inefficiencies become particularly significant during extended hire periods.
Newsome rental AHUs are designed to address these issues through four principal energy-saving technologies.
- Constant Volume Fan Speed Control: Delivering the Airflow You Actually Need
One of the most important factors affecting AHU energy consumption is fan operation.
Traditional fixed-speed fan arrangements operate at essentially the same speed regardless of the actual airflow required. Where the equipment has been selected to accommodate peak conditions, this can result in excessive energy consumption during normal operation.
Newsome rental AHUs incorporate constant volume fan speed control, allowing the required airflow to be selected during installation and commissioning.
Once the airflow has been set, the control system automatically adjusts fan speed to maintain the specified volume as system resistance changes.
This offers two important advantages.
Firstly, commissioning is simplified because engineers can select the required airflow directly, rather than relying on a fixed-speed arrangement that may require additional mechanical balancing.
Secondly, the fans operate at the speed necessary to achieve the required airflow, avoiding the electrical consumption associated with unnecessarily high fan speeds.
Why Reducing Fan Speed Makes Such a Difference
For fans operating under comparable conditions, the relationship between fan speed and power consumption can be approximated using the fan affinity laws.
Fan power varies approximately with the cube of rotational speed:
Fan power ∝ Fan speed³
This means that relatively modest reductions in fan speed can produce substantial reductions in electrical power demand.
| Fan Speed | Approximate Fan Power |
| 100% | 100% |
| 90% | 73% |
| 80% | 51% |
| 70% | 34% |
| 60% | 22% |
For example, reducing fan speed to 70% of its original value can theoretically reduce fan power to approximately 34% of the original consumption.
This represents a potential reduction of around 66% in fan power under the conditions assumed by the affinity laws.
The actual reduction achieved in an AHU installation will depend on system resistance, airflow requirements, motor characteristics and control arrangements. Nevertheless, the principle demonstrates why selecting and maintaining an appropriate airflow can have such a significant impact on energy consumption.
Importantly, Newsome’s constant volume control is intended to maintain the selected airflow, not continually reduce it below the level required by the application. The energy benefit comes from avoiding excessive fan speed while maintaining the necessary ventilation or air handling duty.
- EC Fan Technology: Improved Electrical Efficiency
Newsome rental air handling units utilise electronically commutated (EC) fan technology.
EC fans combine high-efficiency electronically controlled motors with integrated speed regulation, allowing precise control of fan operation across a range of operating conditions.
Compared with conventional AC motor arrangements, appropriately selected EC fans can offer improved electrical efficiency, particularly when operating at part load.
Their principal advantages include improved motor efficiency, precise speed adjustment, reduced electrical losses and effective integration with automatic airflow controls.
What Could EC Fan Efficiency Mean for Operating Costs?
Consider an illustrative comparison between a conventional AC fan arrangement and an equivalent EC fan installation.
If the conventional fan consumes 5.0 kW and the EC arrangement achieves a 15% reduction in electrical demand:
- Conventional AC fan consumption: 5.0 kW
- EC fan consumption: 4.25 kW
- Reduction in electrical demand: 0.75 kW
For an installation operating continuously throughout the year:
0.75 kW × 8,760 hours = 6,570 kWh saved annually
At an illustrative electricity rate of 20p per kWh, this would represent an annual electricity cost reduction of approximately £1,314.
For temporary installations operating over shorter periods, the savings would be proportionate to the actual operating hours.
This example is intended to demonstrate the potential financial impact of improved fan efficiency. Actual performance will depend on the equipment being compared, fan selection, operating duty and installation characteristics.
When combined with Newsome’s constant volume fan speed control, EC technology helps ensure that electrical energy is used effectively to deliver the airflow required.
- Modulating Heating and Cooling Valves: Matching Thermal Output to Demand
Fan electricity consumption is only one part of the energy used by an air handling system.
Where an AHU is connected to a temporary chiller or boiler, the energy required to heat or cool the airstream can be considerably greater than the electrical power consumed by the fans.
Newsome rental AHUs incorporate modulating three-port valves that regulate heating and cooling output in response to the required air temperature.
Rather than operating continuously at maximum thermal output, these valves adjust the proportion of water passing through the heating or cooling coil.
When less heating or cooling is required, a proportion of the water is diverted around the coil, reducing the heat transferred to or from the airstream.
This allows the AHU to respond progressively to changing environmental conditions.
How Modulation Reduces Heating and Cooling Demand
Consider a temporary air handling unit equipped with a 150 kW cooling coil.
Assume the installation operates for 12 hours per day, five days per week, over a 26-week hire period.
If the coil operated continuously at its full rated capacity, the total cooling energy delivered would be:
150 kW × 12 hours × 5 days × 26 weeks = 234,000 kWh of cooling
However, many installations do not require maximum cooling capacity throughout their operating period.
If modulating control results in an average cooling demand equivalent to 50% of the coil’s rated capacity:
75 kW × 12 hours × 5 days × 26 weeks = 117,000 kWh of cooling
This represents a reduction of:
117,000 kWh of cooling energy
If the connected chiller achieves an average coefficient of performance (COP) of 3.0, the difference in cooling energy could correspond to approximately:
117,000 ÷ 3.0 = 39,000 kWh of electrical energy
At an illustrative electricity cost of 20p per kWh, this equates to £7,800.
These figures illustrate the difference between continuous full-load cooling and operation at a lower average load. They should not be interpreted as a guaranteed saving attributable to valve modulation alone. Actual chiller electricity savings depend on the underlying cooling demand, hydraulic arrangement, plant controls, chiller efficiency and operating conditions.
The Importance of Integrated System Control
A modulating valve reduces the thermal duty delivered through the AHU coil, but the resulting energy savings also depend on how the connected heating or cooling plant responds.
For example, a chiller with suitable capacity control may reduce its electrical consumption as cooling demand falls.
Similarly, a boiler operating with appropriate controls can adjust its heating output to match the reduced requirement.
Three-port valves also maintain a bypass water path, so reduced coil demand does not necessarily mean a corresponding reduction in total water flow or pumping energy.
This is why the complete temporary HVAC installation should be considered as an integrated system rather than assessing the AHU in isolation.
Newsome’s experience in temporary chiller hire, boiler hire and air handling systems allows our engineers to consider how the individual components will operate together.
- Integrated Controls and Programmable Scheduling: Avoiding Unnecessary Operating Hours
Even highly efficient equipment will consume unnecessary energy if it operates when heating, cooling or ventilation is not required.
Newsome rental AHUs incorporate integrated controls and programmable time scheduling, allowing operation to be matched to the requirements of the building or process.
Depending on the installation and control configuration, the system can manage start and stop times, fan operation, temperature settings and heating or cooling output.
For buildings that are only occupied during working hours, this can significantly reduce unnecessary energy consumption outside those periods.
The Financial Impact of Operating Hours
Consider an AHU with a combined fan electrical demand of 8 kW.
If the fans operate continuously throughout the year:
8 kW × 8,760 hours = 70,080 kWh annually
If operation is limited to 12 hours per day, five days per week:
8 kW × 3,120 hours = 24,960 kWh annually
The difference is:
45,120 kWh annually
At an illustrative electricity cost of 20p per kWh, this represents £9,024 in annual electricity consumption.
For a 26-week temporary installation, the equivalent reduction would be approximately 22,560 kWh, assuming the same operating pattern and fan demand.
This calculation considers fan electricity alone. Reducing unnecessary AHU operating hours may also reduce the heating and cooling energy required from the associated plant.
Of course, not every application can operate to a reduced schedule. Manufacturing processes, critical environments and facilities requiring continuous ventilation may need their AHUs to operate 24 hours a day.
The advantage of programmable controls is the ability to match operation to the actual requirements of the application rather than relying on continuous operation by default.
Why Energy-Efficient AHUs Matter for Temporary HVAC Installations
Energy efficiency is particularly important when selecting temporary HVAC equipment because rental installations frequently operate under challenging conditions.
An AHU may be required to replace failed equipment, support a production process, provide additional cooling during warmer weather or maintain environmental conditions while permanent plant is being upgraded.
In these circumstances, there is often pressure to restore the required conditions quickly.
However, selecting equipment purely on maximum airflow or heating and cooling capacity can result in higher operating costs if the system is not appropriately matched to the application.
Newsome considers the required airflow, thermal duty, operating hours and associated equipment when specifying a rental AHU.
This helps ensure that the installation provides the necessary performance without introducing avoidable energy consumption.
The Newsome Difference: Designed for Efficient Operation
Not all rental air handling units offer the same level of control or energy efficiency.
The following comparison illustrates the difference between a basic fixed-output rental arrangement and the control features incorporated into Newsome rental AHUs.
| Basic Rental AHU Arrangement | Newsome Rental AHU |
| Fixed-speed fan operation | Adjustable fan speed with constant volume control |
| Conventional AC fan technology | High-efficiency EC fan technology |
| Limited heating and cooling modulation | Modulating three-port heating and cooling valves |
| Basic operating controls | Integrated temperature and system controls |
| Manual start and stop arrangements | Programmable operating schedules |
| Potential for unnecessary full-output operation | Output matched more closely to the installation requirements |
The benefits of these features become particularly relevant for longer-term installations, where even relatively small improvements in operating efficiency can accumulate into meaningful reductions in energy costs.
Technical Support from Specification to Installation
Hiring an energy-efficient AHU is only part of achieving an effective temporary HVAC solution.
Correct equipment selection, installation and commissioning are equally important.
An incorrectly sized AHU may operate inefficiently regardless of the technology it incorporates. Similarly, poorly designed ductwork, excessive system resistance or inappropriate temperature settings can increase energy consumption.
Newsome provides technical support to help customers select equipment appropriate for their application.
Our engineers can assess airflow requirements, heating and cooling duties, installation space, ductwork arrangements and the availability of electrical and hydraulic connections.
Where required, the AHU can also be integrated with Newsome’s temporary chillers, boilers and other HVAC equipment to provide a complete environmental control solution.
This coordinated approach helps ensure that the equipment is not only capable of meeting the required conditions but is configured to operate efficiently throughout the hire period.
Why Rent an Air Handling Unit from Newsome?
Choosing Newsome for temporary air handling unit hire provides access to equipment designed with operating efficiency, controllability and practical installation requirements in mind.
Our rental AHUs combine high-efficiency EC fans, constant volume airflow control, modulating heating and cooling valves and programmable scheduling to help reduce unnecessary energy consumption.
These features can be particularly valuable where equipment is required for extended periods or where electricity and heating or cooling costs represent a significant operational expense.
Combined with Newsome’s experience in temporary HVAC engineering, they provide customers with a practical way to maintain the required environmental conditions while managing the total cost of hire.
The objective is not simply to move more air or deliver maximum heating and cooling output. It is to provide the airflow and thermal capacity required, when they are needed, using energy as efficiently as possible.
Speak to Newsome About AHU Hire
Whether you need temporary ventilation, heating, cooling or a fully integrated air handling solution, Newsome can help specify equipment to meet your operational requirements.
Contact our team today to discuss your temporary AHU hire requirements and find out how our energy-efficient rental equipment could help reduce your operating costs.